GVS Sectionaliser
Ratings
| GVR 15 | GVR 27 | GVR 38 | ||
| Maximum System Voltage | kV | 15.5 | 27 | 38 |
| Continuous Current | A | 630 | 630 | 630 |
| Interrupting Current | kA | 12.5 / 16 | 12.5 | 10 |
| Impulse Voltage Withstand | kV peak | 110 | 125 / 150 | 150 (Internal) 170 (External) |
| Power Frequency Withstand Dry | kVrms for 60 secs | 50 | 60 | 70 |
| Power Frequency Withstand Wet | kVrms for 60 secs | 50 | 50 | 60 |
| Rated Gas Pressure for Above | Atmospheric | Atmospheric / 0.3 bar* | 0.3 bar* gauge | |
| Number of Operations with no maintenance | 10,000 | 10,000 | 10,000 | |
| Weight | Kg | 145 | 145 / 155* | 155 |